US International Building Code: egress, stairs, guards, room sizes (INDICATIVE)

Covers a few IBC items for buildings other than houses: ceiling heights, room width and area, corridor width, egress door size, stair width, risers, treads and guards, and escape window sizes, with hand checks for headroom, landings, thresholds, handrails, ramps and guards. Corridor and stair figures depend on use, chosen per project. Leaves out occupancy, occupant load and capacity, travel distance, exits, fire resistance, structure, accessibility (see the ADA pack) and local amendments. The IBC gives inch figures with rounded metric conversions; Plotlay tests the inch figure.

27rules checked on the drawing
2026.10.1pack version, checked 29 October 2026
1 August 2023instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

International Building Code (IBC), International Code Council

2024 IBC, ICC Digital Codes edition IBC2024V2.0 (first printing August 2023), Chapter 2 (definitions), Chapter 10 (means of egress) and Chapter 12 (interior environment), read on codes.iccsafe.org (free read-only view) 2026-10-29. Compared with the 2021 IBC (IBC2021P2) on the same site: the section numbers used here are the same, except that the 2021 room area rule is 1208.3 (1208.4 in 2024) and 2021 has no 190 sq ft dwelling unit size rule except for efficiency units; the 2024 edition also adds a 36 in guard exception inside R-2 and R-3 units and guard exceptions at occupiable roofs. Source: ICC Digital Codes, 2024 IBC Chapters 10 and 12 (free read-only view).

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Ceiling height of habitable rooms and corridors: 7 ft 6 in2024 IBC 1208.2, 1003.2 (same in 2021)
Ceiling height of bathrooms, toilets, kitchens, storage and laundries: 7 ft2024 IBC 1208.2 (same in 2021)
Habitable rooms at least 7 ft in every direction2024 IBC 1208.1 (same in 2021)
Habitable rooms of a dwelling unit at least 70 sq ft2024 IBC 1208.4 (2021 IBC 1208.3)
Dwelling unit at least 190 sq ft, with one room of 120 sq ft2024 IBC 1208.3, 1208.4 (2021 IBC 1208.3, 1208.4)
Kitchen clear passage: 3 ft2024 IBC 1208.1 (same in 2021)
Corridor width: 36 to 96 in by use2024 IBC 1020.3, Table 1020.3 (same in 2021)
Egress door clear width: 32 in2024 IBC 1010.1.1 (same in 2021)
Egress door clear height: 80 in2024 IBC 1010.1.1 (same in 2021)
Stair width: 44 in, or 36 in for fewer than 50 people2024 IBC 1011.2 (same in 2021)
Stair risers no more than 7 in (7 3/4 in in R-3 and R-2 units)2024 IBC 1011.5.2 and Exception 3 (same in 2021)
Stair risers at least 4 in2024 IBC 1011.5.2 (same in 2021)
Stair treads at least 11 in (10 in in R-3 and R-2 units)2024 IBC 1011.5.2 and Exception 3 (same in 2021)
Guard on the open side of stairs: 42 in (34 in in R-3 and R-2 units)2024 IBC 1015.3 and Exception 3 (same in 2021)
Stair and egress headroom: 80 in2024 IBC 1011.3, 1003.3.1, 1012.5.2 (same figures in 2021)
Stair landings and landings at doors2024 IBC 1011.6, 1010.1.5 (same in 2021)
Door thresholds: 1/2 in2024 IBC 1010.1.6
Handrails: 34 to 38 in, both sides2024 IBC 1014.2, 1011.11 (same in 2021)
Ramps: 1 in 12 slope, 30 in rise, 36 in wide, 60 in landings2024 IBC 202 (Ramp), 1012.2, 1012.3, 1012.4, 1012.5.1, 1012.6 (same in 2021)
Guards where a drop is more than 30 in2024 IBC 1015.2 (same in 2021)
Guard height: 42 in2024 IBC 1015.3
Guard openings: 4 in sphere2024 IBC 1015.4
Emergency escape and rescue openings in R-2, R-3 and R-42024 IBC 1031.2 (same in 2021)
Escape opening net clear area: 5.7 sq ft2024 IBC 1031.3.1 (same in 2021)
Escape opening net clear height: 24 in2024 IBC 1031.3.2 (same in 2021)
Escape opening net clear width: 20 in2024 IBC 1031.3.2 (same in 2021)
Escape opening sill no higher than 44 in2024 IBC 1031.3.3 (same in 2021)