Approved Document M Volume 1, accessible dwellings (England)

Covers the main dimensions of Approved Document M Volume 1 for new dwellings in England: entrance and internal door clear widths, hall widths, the M4(2) stair width, and M4(3) bathroom turning circles and bedroom sizes (measured), plus hand checks for entrance landings, entrance storey WCs, switch heights, kitchen clear space, bedroom access zones and wall strengthening. Pick the category your planning condition requires. Does not cover approach routes, communal areas, lifts, parking, outdoor space or the Part K stair rules.

13rules checked on the drawing
2026.10.1pack version, checked 14 October 2026
1 March 2016instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

The Building Regulations 2010, Approved Document M: Access to and use of buildings, Volume 1: Dwellings (requirements M4(1), M4(2) and M4(3))

2015 edition incorporating 2016 amendments, in force from 1 March 2016 for use in England; the current Volume 1 on gov.uk, seen 2026-10-14. Source: Approved Document M Volume 1: Dwellings, 2015 edition incorporating 2016 amendments (gov.uk).

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Principal entrance door clear openingAD M Vol 1 para 1.14(a) (M4(1)); 2.20(d), 2.21 (M4(2)); 3.22(f), 3.23 (M4(3))
Internal door clear openingAD M Vol 1 para 1.15, Table 1.1 (M4(1)); 2.22(c), Table 2.1 (M4(2)); 3.24(d) (M4(3))
Hall and landing clear widthAD M Vol 1 Table 1.1 (M4(1)); 2.22(a) (M4(2)); 3.24(a) (M4(3))
Stair from the entrance storey at least 850 mm wide (M4(2))AD M Vol 1 para 2.23(c)
Wheelchair accessible bathroom: 1500 mm turning circle (M4(3))AD M Vol 1 para 3.43(e)
Every bedroom at least 8.5 m² (M4(3))AD M Vol 1 para 3.35(d), (f), (i)
Every bedroom at least 2.4 m wide (M4(3))AD M Vol 1 para 3.35(d), (f), (i)
Level landing outside the principal entranceAD M Vol 1 para 2.20(a), (b) (M4(2)); 3.22(a), (b), (d) (M4(3))
WC on the entrance storeyAD M Vol 1 para 1.17 (M4(1)); 2.27 (M4(2)); 3.37 (M4(3))
Switches and sockets 450 mm to 1200 mm above the floorAD M Vol 1 para 1.18 (M4(1)), 2.30 (M4(2)), 3.44 (M4(3))
Clear space in front of kitchen unitsAD M Vol 1 para 2.24(b) (M4(2)); 3.32(b) (M4(3))
Clear access zones in bedroomsAD M Vol 1 para 2.25 (M4(2)); 3.35 (M4(3))
Walls strong enough for grab railsAD M Vol 1 para 2.26 (M4(2))

What it does not cover

Reference only. Approved Documents give one way of meeting the Building Regulations in England; other ways may comply. M4(1) applies to new dwellings by default; M4(2) and M4(3) apply only where a planning condition requires them. Wales, Scotland and Northern Ireland have their own rules. Door clear widths, hall widths, stair width, bathroom turning circles and bedroom sizes are measured; the rest are reminders to check by hand. Your building control body decides compliance.