England Approved Documents K, B and F for new dwellings: stairs, guarding, escape windows (INDICATIVE)

Covers the measurable dwelling items in three Approved Documents: private stair rise, going, pitch, 2R + G and guarding height, guarding at upper-floor opening windows (AD K), and the size and sill height of escape windows (AD B Volume 1), with hand checks for headroom, landings, the 100 mm sphere, handrails, balcony guarding, ramps, which rooms need escape windows and purge ventilation (AD F). Accessible dwelling standards (AD M Volume 1) and space standards are separate packs; fire doors, protected stairways, smoke alarms, structure and energy are not covered.

17rules checked on the drawing
2026.10.1pack version, checked 29 October 2026
30 September 2026instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

The Building Regulations 2010 (England), Approved Documents K (Protection from falling, collision and impact), B Volume 1 (Fire safety: dwellings) and F Volume 1 (Ventilation: dwellings)

Approved Document K, 2013 edition (took effect 6 April 2013, no later amendment listed on gov.uk); Approved Document B Volume 1: Dwellings, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments (the 2026 amendments took effect 30 September 2026; the collated PDF also shows the 2029 amendments, which do not change the figures used here); Approved Document F Volume 1: Dwellings, 2021 edition (took effect 15 June 2022; the 2026 edition takes effect 24 March 2027 with the same purge figures). Read on gov.uk 2026-10-29. Source: Approved Documents K (2013), B Volume 1 (2019 edition incorporating 2020, 2022, 2025 and 2026 amendments) and F Volume 1 (2021), gov.uk, Crown copyright, Open Government Licence.

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Private stair rise: 150 to 220 mmAD K 2013 para 1.3, Table 1.1
Private stair going: 220 to 300 mmAD K 2013 para 1.3, Table 1.1 and note 2
Private stair pitch: 42° at mostAD K 2013 Table 1.1 note 1
Two risers plus a going: 550 to 700 mmAD K 2013 Table 1.1 (note marked *)
Guarding to stairs and landings in a house: 900 mmAD K 2013 paras 1.38, 1.41, 3.2, Diagram 3.1
Opening windows on upper floors: guarding to 800 mmAD K 2013 paras 3.1(a), 3.2, Diagram 3.1 (glazing in all buildings)
Stair headroom: 2 m (loft conversions 1.9 m to 1.8 m)AD K 2013 paras 1.11, 1.13, Diagrams 1.3 and 1.4
Stair landings, open risers and gaps in guarding (100 mm sphere)AD K 2013 paras 1.9, 1.20, 1.21, 1.24, 1.39, 3.3, Diagrams 1.7 and 1.8
Stair handrails: 900 to 1000 mm, both sides if 1 m wide or moreAD K 2013 para 1.34
Guarding to balconies and roof edges: 1100 mm; internal floor edges: 900 mmAD K 2013 paras 3.1, 3.2, Diagram 3.1 and Requirement K2 performance
Ramps: 1:12 for up to 2 m going, 1:15 at 5 m, 1:20 at 10 mAD K 2013 paras 2.3, 2.8, 2.12, 2.14, 2.15, Diagrams 2.1 and 2.2
Escape window openable area: 0.33 m²AD B Vol 1 2019 (2026 amendments) para 2.10(a)(i), para 3.6(a)(i) for flats
Escape window clear width: 450 mmAD B Vol 1 2019 (2026 amendments) para 2.10(a)(ii), para 3.6(a)(ii)
Escape window clear height: 450 mmAD B Vol 1 2019 (2026 amendments) para 2.10(a)(ii), para 3.6(a)(ii)
Escape window: bottom of the opening 1100 mm or less above the floorAD B Vol 1 2019 (2026 amendments) para 2.10(a)(iii), para 3.6(a)(iii)
Which rooms need an escape windowAD B Vol 1 2019 (2026 amendments) paras 2.1 to 2.3, 2.5, 2.11, 2.15, 2.16; flats 3.7, 3.9, 3.13, 3.15 to 3.17
Purge ventilation: openings of 1/20 of the floor area (1/10 for windows opening 15 to 30°)AD F Vol 1 2021 paras 1.26 to 1.31, Table 1.4

What it does not cover