England Approved Document M Volume 2, buildings other than dwellings: doors, corridors, accessible WCs, stairs (INDICATIVE)

Covers the measurable access items for buildings other than dwellings in England: door effective clear widths from Table 2 (new or existing building), corridor width, the size and turning space of a unisex wheelchair-accessible toilet, and stair rise, going, width, risers per flight, 2R + G and guarding height for internal and external stairs. Hand checks cover passing places, toilet fittings, handrails, ramps, the level approach, entrance landings and door details, and headroom. Lifts, car parking, audience seating, hotel bedrooms, changing places toilets, signage and AD B escape widths are not covered.

22rules checked on the drawing
2026.10.1pack version, checked 29 October 2026
1 October 2024instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

The Building Regulations 2010 (England), Approved Document M: Access to and use of buildings, Volume 2: Buildings other than dwellings (requirements M1, M2 and M3), with Approved Document K (Protection from falling, collision and impact) Sections 1 and 2, to which AD M Volume 2 refers for internal stairs and ramps

AD M Volume 2, 2015 edition incorporating 2020 and 2024 amendments (the 2015 edition took effect 1 October 2015; the 2024 amendments, which align it with Approved Document T, took effect 1 October 2024; none of the figures used here changed). AD K 2013 edition (took effect 6 April 2013). Read on gov.uk 2026-10-29. Source: Approved Document M Volume 2, 2015 edition incorporating 2020 and 2024 amendments, and Approved Document K 2013 edition, gov.uk, Crown copyright, Open Government Licence.

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Internal door effective clear width: 800 mm (existing buildings 750 mm)AD M Vol 2 2015 (2020, 2024 amendments) para 3.10(b), Table 2, Diagram 9
External doors used by the public: 1000 mm effective clear width (existing 775 mm)AD M Vol 2 2015 (2020, 2024 amendments) para 2.13(b), Table 2, Diagram 9
Corridor unobstructed width: 1200 mmAD M Vol 2 2015 (2020, 2024 amendments) para 3.14(b)
Corridors under 1800 mm: passing places 1800 by 1800 mmAD M Vol 2 2015 (2020, 2024 amendments) para 3.14(c) to (h)
Unisex wheelchair-accessible toilet: 1500 mm wideAD M Vol 2 2015 (2020, 2024 amendments) para 5.10(e), (i), Diagram 18
Unisex wheelchair-accessible toilet: 1500 by 1500 mm turning spaceAD M Vol 2 2015 (2020, 2024 amendments) para 5.10(i), (p), Diagram 18
Unisex wheelchair-accessible toilet: fittings, rails, door and travel distanceAD M Vol 2 2015 (2020, 2024 amendments) para 5.10, Diagrams 18 and 19
General access stair rise: 150 to 170 mmAD M Vol 2 2015 para 3.51; AD K 2013 para 1.3, Table 1.1
General access stair going: 250 to 400 mmAD M Vol 2 2015 paras 3.50, 3.51; AD K 2013 para 1.3, Table 1.1
Internal stair width: 1200 mm between walls or stringsAD K 2013 para 1.15(a) to (c); AD M Vol 2 2015 para 3.51
General access stair: 2 to 12 risers per flightAD K 2013 para 1.18(a), (b)
External stepped access rise: 150 to 170 mmAD M Vol 2 2015 (2020, 2024 amendments) para 1.33(k), (l)
External stepped access going: 280 to 425 mmAD M Vol 2 2015 (2020, 2024 amendments) para 1.33(m)
External stepped access: flights 1200 mm wideAD M Vol 2 2015 (2020, 2024 amendments) para 1.33(f), (p)
External stepped access: 2 to 12 risers per flight (18 with goings of 350 mm or more)AD M Vol 2 2015 (2020, 2024 amendments) para 1.33(g), (h), Diagram 5
Two risers plus a going: 550 to 700 mmAD K 2013 Table 1.1 (note marked *)
Guarding to stair flights: 900 mmAD K 2013 paras 1.38, 1.40, 3.2, Diagram 3.1
Handrails: 900 to 1000 mm on flights, 900 to 1100 mm on landings, extending 300 mmAD M Vol 2 2015 para 1.37, 3.55; AD K 2013 paras 1.34 to 1.36, Diagrams 1.12 and 1.13
Ramps: 1:12 for up to 2 m going, 1:15 at 5 m, 1:20 at 10 m; 1.5 m wideAD M Vol 2 2015 para 1.26, 3.53, Table 1, Diagram 3; AD K 2013 paras 2.3 to 2.15
Level approach: 1.5 m wide, passing places 1.8 by 2 m, 1:60 or rampsAD M Vol 2 2015 (2020, 2024 amendments) para 1.13
Entrance landing 1500 by 1500 mm, threshold 15 mm, 300 mm beside the door handleAD M Vol 2 2015 (2020, 2024 amendments) paras 2.7(d), (e), 3.10(a), (c), (h)
Headroom: 2 m over stairs and escape routesAD K 2013 paras 1.8, 1.11, 1.12, Diagram 1.3

What it does not cover

Approved Documents give one way of meeting the Building Regulations in England; other ways may comply, and an access statement can justify a different approach, especially in existing buildings. Building control (the local authority or a registered building control approver) decides compliance.