Design codes · New Zealand
NZ Building Code D1 accessible routes (INDICATIVE)
Covers the accessible route figures of D1/AS1: door clear opening, route width and the turning circle in accessible accommodation units (measured), plus hand checks for ramps, door handles and which buildings must be accessible. Use it for public, commercial and communal residential buildings, or as a reference for an accessible home. Does not cover accessible toilets (G1/AS1), parking, lifts, stairs or signs.
Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.
The instrument
New Zealand Building Code clause D1 Access routes, Acceptable Solution D1/AS1 (citing NZS 4121:2001)
D1/AS1 second edition, amendment 6, effective 1 January 2017; listed as current on MBIE Building CodeHub, seen 2026-10-14. Source: MBIE Acceptable Solution D1/AS1 Access Routes (building.govt.nz).
What it checks
Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.
| Rule | Clause |
|---|---|
| Accessible door clear opening at least 760 mm | D1/AS1 7.0.3 |
| Accessible route clear width at least 1200 mm | D1/AS1 2.2.1 |
| Accessible accommodation units: 1500 mm turning circle | D1/AS1 9.2.1 |
| Accessible ramp no steeper than 1:12, 1200 mm wide | D1/AS1 3.1.1, Table 3; 3.1.3; 3.2 |
| Accessible door handles 900 mm to 1200 mm above the floor | D1/AS1 7.0.5 |
| Which buildings must be accessible | Building Act 2004 s 118; Building Code D1.3.2; D1/AS1 1.1.1, 10.1.1 |