National Building Code of Canada 2025, Part 3 exits: stairs, exit doors, corridors, guards (INDICATIVE)

Covers NBC 2025 Part 3 exit stairs, exit doors and corridors for buildings other than houses: stair rise and run, exit stair width, risers per flight, flight height, stair guard height, exit door width and headroom, and public corridor width are measured; handrails, headroom, guard openings, door swing near stairs and ramp slope are hand checks. Does not cover exit numbers, travel distances, occupant load widths, fire separations or stairs inside dwelling units.

15rules checked on the drawing
2026.10.1pack version, checked 29 October 2026
22 December 2025instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

National Building Code of Canada 2025, Division B, Part 3 (Fire Protection, Occupant Safety and Accessibility), Subsections 3.3.1., 3.4.3. and 3.4.6.

NBC 2025, Sixteenth Edition, First Printing, published by the National Research Council of Canada on 2025-12-22 (DOI 10.4224/26fz-gg26), read in the free PDF from the NRC Publications Archive 2026-10-29. Provinces and territories adopt the 2025 edition on their own timetables, and many still enforce a code based on NBC 2020. Source: National Building Code of Canada 2025 (NRC Publications Archive, free PDF).

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Part 3 exits: what this pack testsNBC 2025 Div B 3.4.6.8.(1), 3.4.3.2.
Exit and public stairs: rise 125 to 180 mmNBC 2025 Div B 3.4.6.8.(2)
Exit and public stairs: run at least 280 mmNBC 2025 Div B 3.4.6.8.(1)
Exit stairs: at least 900 mm wideNBC 2025 Div B 3.4.3.2.(8), Table 3.4.3.2.-A
Interior flights: at least 3 risersNBC 2025 Div B 3.4.6.2.(1)
Stair flight: no more than 3.7 m between landingsNBC 2025 Div B 3.4.6.3.(1)
Guards on exit stairs: 1070 mmNBC 2025 Div B 3.4.6.6.(2) and (3)
Guard openings and climbabilityNBC 2025 Div B 3.4.6.6.(5), (6) and (8)
Handrails: 865 mm to 1070 mm, both sides from 1100 mm wideNBC 2025 Div B 3.4.6.5.
Headroom: 2050 mm over exitsNBC 2025 Div B 3.4.3.4.(1) to (3)
Exit doorways: at least 850 mmNBC 2025 Div B 3.4.3.2.(8), Table 3.4.3.2.-A
Exit doorways: 2030 mm headroomNBC 2025 Div B 3.4.3.4.(4) and (5)
Doors near stairs, thresholds and swingNBC 2025 Div B 3.4.6.11.(1) to (3), 3.4.3.3.(2)
Public corridors: 1100 mmNBC 2025 Div B 3.3.1.9.(1) and (2), Table 3.4.3.2.-A
Ramps: 1 in 12 maximumNBC 2025 Div B 3.4.6.7.

What it does not cover

The National Building Code is a model code: it has legal force only where a province or territory adopts it, and each adopts a new edition on its own timetable. Ontario, British Columbia, Alberta, Quebec and others publish their own building codes based on it, with changes, and some cities (for example Vancouver) have their own. Your building official decides compliance with the code and edition they enforce. This pack covers a few Part 3 exit items, not the whole code, and is not a permit review or an exit capacity calculation.