NCC housing notes, Class 1 and 10 (INDICATIVE)

Covers NCC Housing Provisions for houses (Class 1 and 10): minimum ceiling heights by room type, stair risers, goings, 2R + G and riser count, stair balustrade height, and hand checks for headroom, barriers, window protection, wet areas, required facilities and smoke alarms. The figures are the same in NCC 2022 and NCC 2025, so the pack applies whichever edition your state uses. Does not cover structure, fire separation, energy efficiency, condensation, livable housing, state variations or performance solutions.

31rules checked on the drawing
2026.10.1pack version, checked 14 October 2026
1 May 2026instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

National Construction Code 2025 Volume Two and ABCB Housing Provisions Standard 2025 (NCC 2022 still applies in some states: the figures here are the same in both)

NCC 2025, published 1 May 2026, seen on ncc.abcb.gov.au 2026-10-14. ABCB adoption table: VIC from 1 May 2026; ACT from 1 May 2026 with a 12-month transition (NCC 2025 mandatory from 1 May 2027); WA from 1 May 2026 with a 12-month transition (NCC 2022 usable until 30 April 2027); NSW, QLD and TAS from 1 May 2027 (TAS adopted it temporarily from 1 May to 4 June 2026, then reverted to a transition to 1 May 2027); SA from 1 May 2027 for the building code (Volumes One and Two; the plumbing code from 1 May 2026); NT has not adopted NCC 2025. Where NCC 2022 still applies, every figure in this pack is the same in the NCC 2022 Housing Provisions. Source: ABCB Housing Provisions Standard 2025 (NCC 2025); same figures in the 2022 Housing Provisions.

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Ceiling height of habitable rooms (bedrooms, living, study): 2.4 mNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)(a)
Ceiling height of kitchens: 2.1 mNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)(b)
Ceiling height of corridors and passageways: 2.1 mNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)(c)
Ceiling height of bathrooms, laundries and WCs: 2.1 mNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)(d)
Ceiling height of garages, storerooms and pantries: 2.1 mNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)(d)
Ceiling height of other rooms: 2.1 m minimumNCC 2025 Vol Two H4D4; Housing Provisions 10.3.1(1)
Rooms with sloping ceilings or bulkheadsHousing Provisions 10.3.1(1)(e), 10.3.1(2), Figure 10.3.1
Headroom over stairs, ramps and landings: 2.0 mHousing Provisions 10.3.1(1)(f)
Stair riser height 115 to 190 mmNCC 2025 Vol Two H5D2; Housing Provisions 11.2.2(1)(b), Table 11.2.2a
Stair going 240 to 355 mmNCC 2025 Vol Two H5D2; Housing Provisions 11.2.2(1)(b), Table 11.2.2a
Stair slope relationship 2R + G between 550 and 700 mmNCC 2025 Vol Two H5D2; Housing Provisions 11.2.2(1)(b), Table 11.2.2a
Between 2 and 18 risers in each flightNCC 2025 Vol Two H5D2; Housing Provisions 11.2.2(1)(a)
Constant risers and goings, windersHousing Provisions 11.2.2(1)(c), 11.2.2(3), 11.2.2(4)
Open risers and solid treadsHousing Provisions 11.2.2(1)(d), (e)
Barrier where a fall is 1 m or moreHousing Provisions 11.3.3
Stair balustrade at least 865 mm above the nosingsNCC 2025 Vol Two H5D3; Housing Provisions 11.3.4(2)(a)
Barrier height on landings, balconies and decks: 1 mHousing Provisions 11.3.4(2)(b), 11.3.4(3)
Openings in barriersHousing Provisions 11.3.4(4), (5), (7)
Climbable elements where the fall is more than 4 mHousing Provisions 11.3.4(8)
Handrails to stairs and rampsHousing Provisions 11.3.5
Openable bedroom windows above a 2 m fallHousing Provisions 11.3.7
Openable windows in other rooms above a 4 m fallHousing Provisions 11.3.8
Wet-area waterproofing: shower areasNCC 2025 Vol Two H4D2, H4D3; Housing Provisions 10.2.2, 10.2.14 to 10.2.18
Wet-area waterproofing: floors outside the shower and near bathsHousing Provisions 10.2.3, 10.2.4, 10.2.12
Wet-area waterproofing: laundries, WCs, sinks and basinsHousing Provisions 10.2.5
Kitchen sink and cooking facilitiesNCC 2025 Vol Two H4D5; Housing Provisions 10.4.1(1)(a)
Bath or showerHousing Provisions 10.4.1(1)(b)
Clothes washing facilitiesHousing Provisions 10.4.1(1)(c)
Closet pan (WC) and washbasinHousing Provisions 10.4.1(1)(d), (e), 10.4.1(2)
Door to an enclosed WCHousing Provisions 10.4.2
Smoke alarmsNCC 2025 Vol Two H3D6; Housing Provisions 9.5.1, 9.5.2, 9.5.4

What it does not cover

INDICATIVE only. This is not a building permit check: a building surveyor or certifier decides compliance. It covers a few National Construction Code housing provisions (room heights, stairs, barriers, wet areas, facilities, smoke alarms), not the whole code, and ignores state variations and performance solutions. Ceiling heights and stair geometry are measured where the drawing holds them; everything else is a reminder to check by hand. Check which NCC edition applies to your project with your state building regulator.

Check a design against it

Open your project in Plotlay, choose Design codes, pick NCC housing notes, Class 1 and 10 (INDICATIVE) and run the check. It is free in your browser. Step by step: choose the codes for a site and run a code check.