Checks the 2.40 m clear height of habitable rooms (outside houses of Gebäudeklasse 1 and 2), upper floor window sill heights and stair guard heights against the German model building code, with hand checks for where guards are needed, window area for daylight, stairs and barrier-free flats. Stair dimensions (DIN 18065) and barrier-free dimensions (DIN 18040) are paid standards and are left out, and each Land code may differ from the model.

7rules checked on the drawing
2026.10.1pack version, checked 29 October 2026
27 September 2024instrument in effect from

Reference only. Rules are simplified from published sources and may be out of date or incomplete. Verify with the current code and your council, certifier or relevant authority before relying on them.

The instrument

Musterbauordnung (MBO), Fassung November 2002

MBO as last amended by resolution of the Bauministerkonferenz of 26/27 September 2024 (document dated 16 April 2025), read on bauministerkonferenz.de 2026-10-29. The MBO is a model: each Land enacts its own Landesbauordnung from it, with changes and on its own timetable Source: Bauministerkonferenz: Musterbauordnung (free PDF).

What it checks

Each rule names its clause, linked to the published text. Plotlay measures the drawing (rooms, walls, openings, the boundary and the site), uses the facts you enter about the site, and marks each rule pass, fail or check by hand.

RuleClause
Habitable rooms: 2.40 m clear height (not in houses of Gebäudeklasse 1 and 2)MBO 2002 (as amended 2024) § 47(1)
Upper floor window sills: 0.80 m (0.90 m above 12 m)MBO 2002 (as amended 2024) § 38(3)
Guard on the open side of a stair: 0.90 mMBO 2002 (as amended 2024) § 38(1) no. 6 and § 38(4) no. 1
Where guards are needed: drops over 1 mMBO 2002 (as amended 2024) § 38(1) and (4)
Habitable rooms: window opening at least 1/8 of the floor areaMBO 2002 (as amended 2024) § 47(2)
Stairs: a necessary stair to every upper floor, handrailsMBO 2002 (as amended 2024) § 34
Barrier-free flats in buildings with more than two dwellingsMBO 2002 (as amended 2024) § 50(1)